Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | Modular UPS |
Still deciding? Get samples of US$ 500/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Adopting digital control design, and the control system is more reliable |
High input factor 0.99 and output factor 1. |
3-level topology design, efficiency is up to 96% |
Support parallel expansion for cabinet, and parallel expansion is up to 4-6 cabinets. |
Batteries number of each group can be selected from 30 pieces to 50 pieces. |
With 7 inches (standard) and 10 inches (optional) colorful touch LCD screen |
Technical Specification
Module Model | HPM3300E-RM-40 | HPM3300E-RM-50 | |
Cabinet Model | HPM3300E-200/320/400 | HPM3300E-200/300/400/500/600/800/1000 | |
Cabinet capacity (VA) | 200k~400k | 200k~1000k | |
Module capacity (VA) | 40k | 50k | |
Max. Number | 05/8/10 | 4/6/8/10/12/16/20 | |
INPUT | |||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | ||
Operating voltage range | 138~305Vacfor 40% Load; 305~485Vac for 100% Load; | ||
Operating frequency range | 40Hz-70Hz | ||
Power factor | ≥0.99 | ||
Harmonic distortion (THDi) | ≤3% (100% linear load) | ||
Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | ||
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | |||
Bypass Frequency range | Frequency protection range: ±10% | ||
Power Walk In | Support | ||
Generator input | Support | ||
OUTPUT | |||
Rated voltage | 380/400/415Vac, (3Ph+N+PE) | ||
Power factor | 1 | ||
Voltage regulation | ±1% | ||
Output frequency | Line Mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | |
Bat. Mode | (50/60±0.1%)Hz | ||
Crest factor | 0.125694444 | ||
Harmonic distortion (THDv) | ≤1% with linear load; ≤3% with nonlinear load | ||
Efficiency | up to 96% | ||
BATTERY | |||
Battery voltage | Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional); | ||
360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8) | |||
Power module charge current | 20A (Max.) | ||
SYSTEM FEATURES | |||
Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | ||
Overload | Line Mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. | |
Bypass Mode | 135% overload for long term; >1000% overload for 100 ms | ||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | ||
Low battery voltage | Alarm and Switch off | ||
Self-diagnostics | Upon Power On and Software Control | ||
Backfeed | Support | ||
EPO | Shut down UPS immediately (turn to bypass optional) | ||
Battery | Advanced Battery Management | ||
Noise suppression | Complies with EN62040-3 | ||
Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | ||
Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | ||
Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | ||
Communication interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | ||
ENVIRONMENTAL | |||
Operating temperature | 0ºC~40ºC | ||
Storage temperature | -25ºC~55ºC | ||
Humidity range | 0~95% (non condensing) | ||
Altitude | <1500m, derating required when >1500m | ||
Noise level(from 1M distance) | <68dB | <73dB | |
PHYSICAL | |||
Dimension WxD×H (mm) | UPS cabinet | 200/320kVA: 600×850×2000 | 200/300/400kVA: 600×850×2000 |
(S / F) | 400kVA: 1200×850×2000 | ||
Power module | 440×620×130 | ||
Net weight (kg) | UPS cabinet | 210~460 | 200kVA: 240; 300kVA: 260; 400kVA: 290; |
(S / F) | 500kVA: 480; 600kVA: 540; 800kVA: 960; | ||
1000kVA: 1050 | |||
Power module | 33 | 34 | |
STANDARDS | |||
Safety | IEC/EN62040-1, IEC/EN62477-1 | ||
EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) |