Power Input | AC Input Signals | 208 or 416 Volt nominal line to and 5Amp Cts with a minimun 6.25VA Rating internal 0.25 ohm burden resistors |
Line to line Voltages | Per table below | |
DC Supply | 18-36 VDC (Transient and reverse voltage protected) for 12 VDC Applicationis use LSM 672-12 |
|
Polarity | Negative ground (case isolated) | |
DC Power Consumption | 70 ma continuous | |
Power output Signal | 0-7 Volts based on 5amps of C.T .output | |
Performance | Load sharing | Adjustable to within ±2% between sets |
Performance | Isochronous and droop paralleling and power contol | |
Reverse Power Monitor | Adjustable from 0.5-20% with a 2 second inverse time constant | |
Forward power Monitor | "ON" trip point adjustable from 20-100%/ "OFF" trip point adjutable From 20-100%. Normally open contacts with a 2 second inverse time Constant |
|
Power output Signal | 0 to 7.5 Volts DC representing 0-100% load. All performance Specifications are based on 5A from the current transformer(CT) Secondaries at full load unity P.F. |
|
Droop Range | 1-5% regulation | |
Environmental | Temperature Range | -40 to +175°F(-40°+85 °C) |
Relative Humidity | 100%- Circuit board heavily conformal coated | |
All Surface Finishes | Fungus Proof and Corrosion Resitant | |
Reliability | Testing | 100% Functional Tested |
Vibration | 1g @ 20-100HZ | |
Shock | 10gs | |
physical | Dimensions | See Diagram 1 |
Weight | 5.2 Lbs (2.36Kgs) | |
Mounting | Any position, Vertical Preferred |