Module Model |
HPM3300E-RM-40 |
HPM3300E-RM-50 |
Cabinet Model |
HPM3300E-200/320/400 |
HPM3300E-200/300/400/500/600/800/1000 |
Cabinet capacity (VA) |
200k~400k |
200k~1000k |
Module capacity (VA) |
40k |
50k |
Max. Number |
05/8/10 |
4/6/8/10/12/16/20 |
INPUT |
Nominal voltage |
380/400/415Vac, (3Ph+N+PE) |
Operating voltage range |
138~305Vacfor 40% Load; 305~485Vac for 100% Load; |
Operating frequency range |
40Hz-70Hz |
Power factor |
≥0.99 |
Harmonic distortion (THDi) |
≤3% (100% linear load) |
Bypass voltage range |
Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) |
|
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) |
Bypass Frequency range |
Frequency protection range: ±10% |
Power Walk In |
Support |
Generator input |
Support |
OUTPUT |
Rated voltage |
380/400/415Vac, (3Ph+N+PE) |
Power factor |
1 |
Voltage regulation |
±1% |
Output frequency |
Line Mode |
Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) |
Bat. Mode |
(50/60±0.1%)Hz |
Crest factor |
0.125694444 |
Harmonic distortion (THDv) |
≤1% with linear load; ≤3% with nonlinear load |
Efficiency |
up to 96% |
BATTERY |
Battery voltage |
Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional); |
360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8) |
Power module charge current |
20A (Max.) |
SYSTEM FEATURES |
Transfer time |
Utility to Battery : 0ms; Utility to bypass: 0ms |
Overload |
Line Mode |
≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. |
Bypass Mode |
135% overload for long term; >1000% overload for 100 ms |
Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
Low battery voltage |
Alarm and Switch off |
Self-diagnostics |
Upon Power On and Software Control |
Backfeed |
Support |
EPO |
Shut down UPS immediately (turn to bypass optional) |
Battery |
Advanced Battery Management |
Noise suppression |
Complies with EN62040-3 |
Audible & Visual alarms |
Line Failure, Battery Low, Overload, System Fault |
Status LED & LCD display |
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault |
Reading on the LCD display |
Input, Output, Battery, Command, Setting, Maintenance |
Communication interface |
RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) |
ENVIRONMENTAL |
Operating temperature |
0ºC~40ºC |
Storage temperature |
-25ºC~55ºC |
Humidity range |
0~95% (non condensing) |
Altitude |
<1500m, derating required when >1500m |
Noise level(from 1M distance) |
<68dB |
<73dB |
PHYSICAL |
Dimension WxD×H (mm) |
UPS cabinet |
200/320kVA: 600×850×2000 |
200/300/400kVA: 600×850×2000 |
(S / F) |
400kVA: 1200×850×2000 |
Power module |
440×620×130 |
Net weight (kg) |
UPS cabinet |
210~460 |
200kVA: 240; 300kVA: 260; 400kVA: 290; |
(S / F) |
500kVA: 480; 600kVA: 540; 800kVA: 960; |
|
1000kVA: 1050 |
Power module |
33 |
34 |
STANDARDS |
Safety |
IEC/EN62040-1, IEC/EN62477-1 |
EMC |
IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) |