Technical Specification |
|
UD10 / UD10L |
UD15 / UD15L |
UD20 / UD20L |
UD30 / UD30L |
UD40L |
UD60L |
UD80L |
Capacity (VA/Watts) |
10K / 9K |
15K / 13.5K |
20K / 18K |
30K / 27K |
40K / 36K |
60K / 54K |
80K / 72K |
INPUT |
|
Nominal Voltage |
380/400/415Vac(3Ph+N+PE) |
Operating Voltage Range |
208~478Vac@half load; 305~478Vac@full load |
Operating Frequency Range |
50Hz:45~55Hz,60Hz:54~66Hz |
Power Factor |
≥0.99 |
|
Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) |
Bypass Voltage Range |
230V:+20%(Optional +10%,+15%) |
|
240V:+15%(Optional +10% ) |
|
Min. voltage: -45% (Optional -10%, -20%,-30%) |
ECO Range |
Same as bypass |
Harmonic Distortion (THDi) |
≤3%(100% non-linear load) |
OUTPUT |
|
Output Voltage |
380/400/415Vac(3Ph+N+PE) |
Power Factor |
0.9 |
Voltage Regulation |
±1% |
Frequency |
Line Mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) |
Bat. Mode |
50/60(1±0.1%)Hz |
Crest Factor |
3:01 |
Harmonic Distortion (THDv) |
≤2% with linear load |
≤5% with non-linear load |
Waveform |
Pure Sinewave |
Transfer Time |
Utility to Battery : 0ms; Utility to Bypass: 0ms |
EFFICIENCY |
|
Efficiency |
95% |
BATTERY |
|
Battery |
Standard unit |
±120Vdc (20pcs 12V9AH) |
±120Vdc (2x20pcs 12V9AH) |
±120Vdc (3x20pcs 12V9AH) |
N/A |
Voltage |
Long run unit |
Selectable Voltage:±96V/±108V/±120Vdc |
Selectable Voltage:±192V/±204V/±216V/ ±228V/±240Vdc |
Charging |
Standard unit |
1.35 |
2.7 |
4.05 |
N/A |
Current (A) |
Long run unit |
Max.current 10A |
Max.current 15A |
Max.current 30A |
PROTECTI |
ON |
|
|
Line Mode |
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately |
Overload |
Bat. Mode |
Load≤110%: last 10min, ≤125%: last 1min, ≤150%: last 5S, ≥150% shut down UPS immediately |
|
Bypass Mode |
20A(Input breaker) |
32A(Input breaker) |
40A(Input breaker) |
63A(Input breaker) |
80A(Input breaker) |
100A(Input breaker) |
125A(Input breaker) |
Short Circuit |
Hold Whole System |
Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
Battery Low |
Alarm and Switch off |
INDICATORS |
|
Audible & Visual Alarms |
Line Failure, Battery Low, Overload, System Fault |
Status LED & LCD Display |
Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
Parameters On The LCD Panel |
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time |
MANAGEMENT |
|
Communication Interface |
RS-232,RS-485,USB,Parallel card, SNMP card(Optional), Relay card (Optional),Battery temperature sentor(optional) |
ENVIRONMENT |
|
Operating Temperature |
0~40ºC |
Storage Temperature |
-25~55ºC |
Humidity Range |
0~95% (Non-condensing) |
Altitude |
< 1500m |
Noise Level |
<55dB |
<58dB |
<63dB |
PHYSICAL |
|
Dimension W×D×H (mm) |
250×828×868 |
360×828×868 |
Net Weight (kg) |
115/57 |
170/63 |
171/64 |
223/71 |
73 |
118 |
122 |
STANDARDS |
|
Noise Suppression |
Complies with EN62040-2 |
Safety |
IEC/EN62040-1,IEC/EN60950-1 |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, |
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
Specifications are subject to change withour notice in advanced |