Model |
HPM3300E-RM-40 |
HPM3300E-RM-50 |
HPM3300E-RM-60 |
Cabinet Model |
HPM3300E-80 |
HPM3300E-120 |
HPM3300E-100 |
HPM3300E-150 |
HPM3300E-120 |
Cabinet capacity (VA) |
40k~80k |
40k~120k |
50k~100k |
50k~150k |
60k~120k |
Module capacity (VA) |
40k |
50k |
60k |
Max. number |
2+1 |
3 |
2+1 |
3 |
2+1 |
Input |
Nominal voltage |
380/400/415Vac, (3Ph+N+PE) |
Operating voltage range |
138~305Vac for 40% load; 305~485Vac for 100% load |
Operating frequency range |
40Hz~70Hz |
Power factor |
≥0.99 |
Harmonic distortion (THDi) |
≤3% (100% linear load) |
Bypass voltage range |
Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) |
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) |
Bypass frequency range |
±10% |
Power Walk In |
Support |
Generator input |
Support |
Output |
Rated voltage |
380/400/415Vac, (3Ph+N+PE) |
Power factor |
1 |
Voltage regulation |
±1% |
Output |
Line mode |
Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) |
frequency |
Bat. mode |
(50/60±0.1%)Hz |
Crest factor |
03:01 |
Harmonic distortion (THDv) |
≤2% with linear load; ≤4% with nonlinear load |
Efficiency |
96.50% |
Battery |
|
VRLA battery |
360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no power |
Battery voltage |
derating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8) |
|
Lithium battery |
512Vdc |
Power module charge current |
20A (Max.) |
System features |
Transfer time |
Utility to Battery : 0ms; Utility to Bypass: 0ms |
Overload |
Line mode |
≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately |
Bypass mode |
30ºC:135% overload for long term; 40ºC:125% overload for long term; 1000% overload for 100 ms |
Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
Low battery voltage |
Alarm and Switch off |
Self-diagnostics |
Upon Power On and Software Control |
Backfeed protection |
Support |
Battery |
Advanced Battery Management |
Noise suppression |
Complies with EN62040-3 |
Audible & visual alarms |
Line Failure, Battery Low, Overload, System Fault |
Status LED & LCD display |
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault |
Reading on the LCD display |
Input, Output, Battery, Command, Setting, Maintenance |
Communication interface |
RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) |
Operation Environment |
Operating temperature |
0ºC~40ºC |
Storage temperature |
-25ºC~55ºC |
Humidity range |
0~95% (non condensing) |
Altitude |
<1500m, derating required when >1500m |
Noise level |
<57dB |
<58dB |
<62dB |
Physical |
Dimension |
UPS cabinet |
485×850×620 |
W×D×H (mm) |
Power module |
440×620×130 |
Net weight (kg) |
UPS cabinet |
103 |
113 |
110 |
Power module |
33 |
34 |
35 |
Standards |
Safety |
IEC/EN62040-1, IEC/EN62477-1 |
EMC |
IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) |