Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
True double-conversion
Real-time digital signal processor (DSP) control
N+X parallel redundancy
Selectable quantity of battery for each group:for long run unit
Adjustable charging current via LCD
3-stage charging design optimizes battery performance
ECO mode operation for energy saving
Self-diagnosis at startup
Emergency power off function(EPO)
Maintenance bypass is convenient for maintenance
Generator compatible
Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
Cold start
MODEL | UCR60L | UCR100L | ||||
Capacity (VA/Watts) | 6K / 5.4K | 10K / 9K | ||||
INPUT | ||||||
Nominal Voltage | 380/400/415Vac(3Ph+N+PE) or 220/230/240Vac(L+N+PE) | |||||
Operating Voltage Range |
208~478Vac or 120VAC-276Vac | |||||
Operating Frequency Range |
50Hz:45~55Hz,60Hz:54~66Hz | |||||
Power Factor | ≥0.99 | |||||
Bypass Voltage Range |
Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) | |||||
230V:+20%(Optional +10%,+15%) | ||||||
240V:+15%(Optional +10% ) | ||||||
Min. voltage: -45% (Optional -20%,-30%) | ||||||
ECO Range | Same as bypass | |||||
Harmonic Distortion (THDi) |
≤5%(100% non-linear load) | |||||
OUTPUT | ||||||
Output Voltage | 220/230/240Vac | |||||
Power Factor | 0.9 | |||||
Voltage Regulation | ±1% | |||||
Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) | ||||
Bat.Mode | (50/60±0.1)Hz | |||||
Crest Factor | 3:1 | |||||
Harmonic Distortion (THD) |
≤2% with linear load | |||||
≤5% with non-linear load | ||||||
Waveform | Pure Sinewave | |||||
Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||||
EFFICIENCY | ||||||
Efficiency | Up to 94% | |||||
BATTERY | ||||||
Battery Voltage | Selectable Voltage: ±96/108/120Vdc | |||||
Typical Recharge Time | 6-8 hours (To 90% capacity) | |||||
Charging Current | Maximum current 10A | |||||
PROTECTION | ||||||
Overload | Line Mode | Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode | ||||
Bypass Mode | 40A(Input breaker) | 63A(Input breaker) | ||||
Short Circuit | Hold Whole System | |||||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||
Battery Low | Alarm and Switch off | |||||
INDICATORS | ||||||
Audible &Visual Alarms | Line Failure, Battery Low, Overload, System Fault | |||||
Status LED &LCD Display | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault | |||||
Parameters On The LCD Panel |
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time | |||||
MANAGEMENT | ||||||
Communication Interface | RS-232,USB,Parallel card, SNMP card(Optional), Relay card (Optional) | |||||
ENVIRONMENT | ||||||
Operating Temperature | 0ºC~40ºC | |||||
Storage Temperature | -25ºC~55ºC | |||||
Humidity Range | 0~95% (Non-condensing) | |||||
Altitude | < 1500m | |||||
Noise Level | <55dB | |||||
PHYSICAL | ||||||
Dimension W×H×D (mm) | 443×131×580(3U) | |||||
Net Weight (kg) | 30 | 31 | ||||
STANDARDS | ||||||
Noise Suppression | Complies with EN62040-2 | |||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, | |||||
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | ||||||
BATTERY PACK | ||||||
Model | EXBR±120V | |||||
Battery type& Max.quantity |
7Ah×20/9Ah×20 | |||||
Dimensions W×H×D (mm) |
443×131×720(3U) | |||||
Net Weight (kg) | 67 |